PS 865 - Beam Clamp
Can be used with PS 871 Safety Anchor Strap
Part No. | Rod Size | B | C | D | E | Finish | Product Weight / Piece (lbs) |
---|---|---|---|---|---|---|---|
PS 865 1/2"-13 | 1/2"-13 | 1/4" (6) | 1/2 x 2 | 1-11/16" (43) | 15/16" (24) | EG | 2.01 |
PS 865 3/8"-16 | 3/8"-16 | 3/16" (5) | 1/2 x 2 | 1-11/16" (43) | 29/32" (23) | EG | 1.56 |
PS 865 5/8"-11 | 5/8"-11 | 5/16" (8) | 5/8 x 2 | 1-11/16" (43) | 1-5/16" (33) | EG | 3.11 |
Design Loads
Design Loads - PS 865 | |
---|---|
Part Number | Design Load lbs (kN) |
PS 865 3/8" | 1,100 |
PS 865 1/2" | 1,600 |
PS 865 5/8" | 2,400 |
Notes:
- Design loads only apply to Power-Strut brand products.
- Safety factor = 2.5 based on ultimate strength of connection.
- For beam flanges between 3/4" (19.1 mm) to 1-5/8" (41.3 mm) thick.
- Set Screw Installation Torque:
PS 865 3/8", PS 865 1/2": 125 in-lbs (14 N-m)
PS 865 5/8": 250 in-lbs (28 N-m)
General Specifications
Standard Dimensions (Unless Shown Otherwise on Drawing):
- Hole Diameter: 9/16" (14mm)
- Hole Spacing (From End): 13/16" (21mm)
- Hole Spacing (On-Center): 1 7/8" (48mm)
- Width: 1 5/8" (41mm)
- Thickness:
- 1/4" (6.4mm) with steel meeting or exceeding ASTM A1011 SS GR 33, or
- 0.220" (5.6mm) with steel meeting or exceeding ASTM A1011 HSLAS GR 45
Note:
- When used for mechanical supports, load capacities of brackets and fittings should be in compliance with the American Standard Code for Pressure Piping.
Materials & Finishes
Materials & Finishes:
- Electrogalvanized (EG): Conforms to ASTM B633, Type III SC1 or SC3
Related Resources
Videos
CAD Files
Miscellaneous
- Cancellation & Modification Policy
- Cold-Forming Strength Increase
- CSI MasterSpec (05430)
- FAQ
- LEED Version 4
- Let's Talk Strut Installation
- Materials & Finishes
- Outdoor Applications
- Return Policy
- Safety Data Sheet (SDS) Galvanized Products: EG, HG, ZD
- Safety Data Sheet (SDS) Metal Framing, Channel Galvanized Products: PG
- Safety Data Sheet (SDS) Metal Framing, Channel Non-Galvanized Products: GR